Case: T07FR00276

Parcel: 10119001F

Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE LIQUIDS

Date Description Inspector Results Comments
06/07/2007 VIOL - FLAMMABLE LIQUIDS Approved Tanks were inerted to less than 5% O2 with dry ice. The two 1000 gallon union distributors tanks were removed.
02/12/2007 VIOL - FLAMMABLE LIQUIDS Violation UFC 3404.2.14.1- Removal. Prior to removing these tanks, a permit shall be obtained. They shall be pumped out (empty) and purged before transporting. Tank openings shall be capped or plugged, leaving a .125 inch to .250 inch diameter opening for pressure equalization. They shall be transported appropriately.