Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
| Date |
Description |
Inspector |
Results |
Comments |
| 06/07/2007 |
VIOL - FLAMMABLE LIQUIDS |
|
Approved |
Tanks were inerted to less than 5% O2 with dry ice. The two 1000 gallon union distributors tanks were removed. |
| 02/12/2007 |
VIOL - FLAMMABLE LIQUIDS |
|
Violation |
UFC 3404.2.14.1- Removal. Prior to removing these tanks, a permit shall be obtained. They shall be pumped out (empty) and purged before transporting. Tank openings shall be capped or plugged, leaving a .125 inch to .250 inch diameter opening for pressure equalization. They shall be transported appropriately. |