Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/06/2007

Applicant:

LAZY 8 MOTEL LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T07FR00273
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
02/06/2007 INSP - FULL JDAVIS Correction Required
02/06/2007 VIOL - MEANS OF EGRESS JDAVIS Correction Required 1. 1008.1.8.3 Locks and latches. 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background.: -Main front doors. 2. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. - Remove the slide bolts on the active leaf of the exit doors. 3. Section 1014.2 Exit or exit access doorway arrangement. Required exits shall be located in a manner that makes their availability obvious. Exits shall be unobstructed at all times. Exit and exit access doorways shall be arranged in accordance with Sections 1014.2.1 and 1014.2.2.: -maintain all exity free of obstructions including high chairs and other waiter equipment.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00273
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
02/06/2007 VIOL - BUILDING SVCS & SYSTEMS JDAVIS Approved 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. - Replace the broken cover plate on the NE corner of the bar area.
02/06/2007 VIOL - BUILDING SVCS & SYSTEMS JDAVIS Approved 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. - Remove the extension cord in the NE corner of the bar area.
02/06/2007 VIOL - BUILDING SVCS & SYSTEMS JDAVIS Approved 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. - Storage room #1
02/06/2007 VIOL - FIRE PROTECTION SYSTEMS JDAVIS Approved 1. Section 904 Extenquishing Systems: Hood system sahll be cleaned from the roof down including replacing the link and removing grease build up on the cable linking system. - Currently in progress 2. All equipment must be at least 6 inches under the hood.
02/06/2007 VIOL - COMPRESSED GASES JDAVIS Approved Section 3003.3 Compressed gas cylinders All compressed gas cylinders shall be secure to prevent accidental dislodgemnt: - rear yard - bar -storage room