Case: T07FR00273

Parcel: 119010740


Addresses:

310 E BENSON HY

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
02/06/2007 VIOL - BUILDING SVCS & SYSTEMS Approved 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
- Storage room #1
02/06/2007 VIOL - BUILDING SVCS & SYSTEMS Approved 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
- Remove the extension cord in the NE corner of the bar area.
02/06/2007 VIOL - BUILDING SVCS & SYSTEMS Approved 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
- Replace the broken cover plate on the NE corner of the bar area.