Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR00023
Case Details
Entered Date:
01/03/2007
Applicant:
DND NEFFSON CO
Description:
Full fire Inspection done by John Bieg on 1-3-07.
Outstanding Inspections
Case Number: T07FR00023
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. 1. Remove storage from blocking access to first floor sprinkler riser pipe. |
01/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. 1. Remove storage from blocking electrical service equipment, in first floor escalator service room. 2. Remove storage from blocking electrical service equipment, in second floor accessory stock room. |
01/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 1. Remove cube adaptor, in first floor break room. |
01/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1. Remove extension cord, in loss prevention office. Call me if you have any questions at 791-4014, Ext. 122 |
01/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Service extinguisher in first floor loading dock room. 2. Inspect, test, and maintain automatic sprinkler system. Affix current service tag to the system. 3. Service extinguisher in loss prevention office. 4. Replace missing extinguisher, on second floor, by missy display. 5. Service extinguisher in second floor, shoe stock room. 6. Service extinguisher in second floor, CCTV room. |
01/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. 1. Remove Pepsi machine from blocking the extinguisher, in first floor break room. 2. Remove items from obstructing the fire extinguisher in the second floor CCTV room. |
01/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. 1. Extinguisher in second floor elevator mechanical room shall be mounted on the wall. |
01/03/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. 1. Remove storage from first floor exit corridor. 2. Remove storage from exit corridor, on first floor by team room. 3. Remove storage from exit discharge, on second floor by visual. 4. Remove storage from exit discharge, on second floor by women's fitting room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00023
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2007 | INSP - FULL | JBURGE | Approved | Re-inspection: All Tucson Fire Code violations were corrected 1-18-07. Inspector John Bieg |