Case: T07FR00023

Parcel: 10511061P


Addresses:

4510 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00023

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
1. Remove storage from blocking electrical service equipment, in first floor escalator service room.
2. Remove storage from blocking electrical service equipment, in second floor accessory stock room.
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.
1. Remove cube adaptor, in first floor break room.
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
1. Remove extension cord, in loss prevention office.


Call me if you have any questions at 791-4014, Ext. 122