Case: T07FR00023

Parcel: 10511061P


Addresses:

4510 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00023

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
1. Service extinguisher in first floor loading dock room.
2. Inspect, test, and maintain automatic sprinkler system. Affix current service tag to the system.
3. Service extinguisher in loss prevention office.
4. Replace missing extinguisher, on second floor, by missy display.
5. Service extinguisher in second floor, shoe stock room.
6. Service extinguisher in second floor, CCTV room.
01/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view.
1. Remove Pepsi machine from blocking the extinguisher, in first floor break room.
2. Remove items from obstructing the fire extinguisher in the second floor CCTV room.
01/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely
anchored to the mounting surface in accordance with the manufacturer’s installation instructions.
1. Extinguisher in second floor elevator mechanical room shall be mounted on the wall.