Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/03/2007

Applicant:

BROADWAY POWER CENTER GROUP LLC

Description:

Full FPI completed 1/2/07

Outstanding Inspections

Case Number: T07FR00012
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
01/03/2007 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required 304.1 - General Housekeeping. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. _____ Remove waste and store stock in an approved manner.
01/03/2007 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required 304.1.1 Waste material. Accumulations of ... litter or combustible or flammable waste or rubbish of any type shall not be permitted... _____ Metal shavings and sawdust shall be prevented from accumulating around saws.
01/03/2007 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required TFC 315.2.1 Sprinkler Clearance. Storage shall be maintained ... a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____ Remove storage to 18 inches or more below sprinkler head.
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.1 - Identified electrical hazards shall be abated. _____ Replace frayed power plug on heat gun with UL or FM approved plug.
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.3 - Blocked electrical panel. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel in an approved manner.
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. _____ Remove extension cord and/or replace with approved permanent electrical power source. (Sign, front window) _____ Power strip shall be plugged directly into wall. (under workbench, west wall of workshop) _____ Remove extension cord and/or replace with approved permanent electrical power source. (night light, rear door)
01/03/2007 VIOL - FIRE RESIST.RATED CONST DGREENLE Correction Required TFC 703.1 - Missing/Damaged Ceiling Tiles. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____ Replace missing and damaged ceiling tiles.
01/03/2007 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 901.6 - Fire Extinguisher. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Extinguishers shall be inspected and tagged. (back room)

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00012
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
01/03/2007 VIOL - MEANS OF EGRESS DGREENLE Approved 1027.3 - A means of egress shall be free from obstructions that would prevent its use (24" in non-public areas). _____ Maintain a route for exiting workshop through rear door. _____ Maintain a route for exiting from behind counter through front door.
01/03/2007 VIOL - MEANS OF EGRESS DGREENLE Approved 1023.6 - The exit discharge shall provide a direct and unobstructed access to a public way. _____ Dumpster shall be removed from path of egress. (rear door)
05/03/2007 INSP - FULL DGREENLE Approved C of O still in progress Houskeeping issues ongoing