Case: T07FR00012

Parcel: 133231430


Addresses:

7831 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T07FR00012

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/03/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required 304.1.1 Waste material. Accumulations of ... litter or combustible or flammable waste or rubbish of any type shall not be permitted...

_____ Metal shavings and sawdust shall be prevented from accumulating around saws.
01/03/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required 304.1 - General Housekeeping. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises.

_____ Remove waste and store stock in an approved manner.
01/03/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2.1 Sprinkler Clearance. Storage shall be maintained ... a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.

_____ Remove storage to 18 inches or more below sprinkler head.