Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. _____ Remove extension cord and/or replace with approved permanent electrical power source. (Sign, front window) _____ Power strip shall be plugged directly into wall. (under workbench, west wall of workshop) _____ Remove extension cord and/or replace with approved permanent electrical power source. (night light, rear door) |
|
| 01/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.1 - Identified electrical hazards shall be abated. _____ Replace frayed power plug on heat gun with UL or FM approved plug. |
|
| 01/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.3 - Blocked electrical panel. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel in an approved manner. |