Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR00012

Parcel: 133231430


Addresses:

7831 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00012

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring.

_____ Remove extension cord and/or replace with approved permanent electrical power source. (Sign, front window)

_____ Power strip shall be plugged directly into wall. (under workbench, west wall of workshop)

_____ Remove extension cord and/or replace with approved permanent electrical power source. (night light, rear door)
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 - Identified electrical hazards shall be abated.

_____ Replace frayed power plug on heat gun with UL or FM approved plug.
01/03/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3 - Blocked electrical panel. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

_____ Clear area in front of electrical panel in an approved manner.