Case: T07FR00009
Case Details
Entered Date:
01/02/2007
Applicant:
DND NEFFSON CO
Description:
Full fire Inspection done by Inspector John Bieg 1-2-07
Outstanding Inspections
Case Number: T07FR00009
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. 1. Remove storage from around water heater, in second floor janitor's closet, inside southwest stock room. 2. Remove storage from isles, in second floor kids stock room. 3. Remove storage from isles, in second floor west stock room. 4. Remove storage from isles, on second floor by roof access stairway. |
01/02/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Sprinkler heads shall not be obstructed. Two sprinkler heads obstructed in second floor home fasion stock room, along the southwest wall. 2. Sprinkler heads shall not be obstructed. Two sprinkler heads obstructed in second floor paint department, northwest side. |
01/02/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. 1. Remove storage from electrical room, in second floor kids stock room. 2. Remove storage from electrical pannel, in second floor, southeast side of paint stock room. 3. Remove storage from electrical room, second floor main storage area northwest side. 4. Remove storage from first floor mechanical room. |
01/03/2007 | VIOL - ADMINISTRATION | JBURGE | Correction Required | TFC 107.1 Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. 1. Replace FDC inlet caps on automatic sprinkler connections. 2. Panic hardware shall be continuously maintained. Repair panic hardware on southwest exit door in first floor repair garage. If you have any questions call me at 791-4014, Ext. 122 |
01/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. 1. Remove storage from blocking electrical service equipment, first floor Dental records storage area. |
01/03/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.4 Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure.Awritten record shall be maintained and be available to the fire code official. 1. Roll-up fire door shall be inspected and tested annually. In first floor tire sales. |
01/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the the manufacturer’s installation instructions. 1. The extinguisher shall be mounted in the elevator electrical room. |
01/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters “FDC” at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official. 1. The FDC connection on the northwest side of the building shall be visible to approaching fire apparatus. Post a sign indicating FDC connection, automatic sprinkler connection. |
01/03/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. 1. Remove storage from exit corridor, first floor, dental west exit corridor. |
01/03/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1. Replace missing door knob on exit door, first floor fashion stock room. 2. Remove door knob on exit door with panic hardware, first floor, dental corridor exit on west side of building. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00009
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-16-07. Inspector John Bieg. |