Case: T07FR00009

Parcel: 10511061A


Addresses:

4570 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00009

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/03/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
1. Replace missing door knob on exit door, first floor fashion stock room.
2. Remove door knob on exit door with panic hardware, first floor, dental corridor exit on west side of building.
01/03/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building
element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
1. Remove storage from exit corridor, first floor, dental west exit corridor.
01/02/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated.
1. Exit sign shall be illuminated, second floor PMT, stair 6 door 2.