Case: T07FR00009

Parcel: 10511061A


Addresses:

4570 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T07FR00009

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/02/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.
1. Remove storage from electrical room, in second floor kids stock room.
2. Remove storage from electrical pannel, in second floor, southeast side of paint stock room.
3. Remove storage from electrical room, second floor main storage area northwest side.
4. Remove storage from first floor mechanical room.
01/02/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
1. Remove storage from around water heater, in second floor janitor's closet, inside southwest stock room.
2. Remove storage from isles, in second floor kids stock room.
3. Remove storage from isles, in second floor west stock room.
4. Remove storage from isles, on second floor by roof access stairway.
01/02/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
1. Sprinkler heads shall not be obstructed. Two sprinkler heads obstructed in second floor home fasion stock room, along the southwest wall.
2. Sprinkler heads shall not be obstructed. Two sprinkler heads obstructed in second floor paint department, northwest side.