Case: T06FR02954
Case Details
Entered Date:
12/29/2006
Applicant:
DND NEFFSON CO
Description:
Full Fire Inspection Done By John Bieg on 12-29-06.
Outstanding Inspections
Case Number: T06FR02954
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. 1. Exit sign shall be illuminated, in second floor employee entrance. 2. Exit sign shall be illuminated, in second floor by the Men's dept. |
01/02/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. 1. Secure helium tank in second floor conference room. If you have any questions call 791-4502. |
12/29/2006 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. 1. Storage around, and on top of flamable liquids cabinet shall be removed. {first floor visual room}. |
12/29/2006 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Sprinkler head obstructed in first floor dress stock room. Sprinkler heads shall be no less than 18 inches from storage. 2. Sprinkler heads shall not be obstructed. Remove shelves from obstructing sprinkler heads in second floor package check room. 3. Sprinkler heads shall not be obstructed. Remove storage from sprinkler head, in east hallway of loss prevention offices. 4. Sprinkler heads shall not be obstructed. Remove top level of storage rack in second floor Men's shoe dept. 5. Sprinkler heads shall not be obstructed. Remove top level of storage rack in second floor office supply room. |
12/29/2006 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. 1. Remove storage from elevator service room {first floor}. 2. Remove storage from electrical room, by the elevator service room {first floor}. 3. Remove storage from first floor elevator electrical room. 4. Remove storage from electrical room, in second floor loading dock. 5. Remove storage from electrical room, by second floor men's dept. 6. Remove storage from electrical room, second floor west of elevator. |
12/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1. Remove two extension cords,{yellow and brown} from first floor sign room. 2. Remove extension cord in second floor employee break room, used for direct TV. {Replace with a fused powerstrip}. 3. Remove extension cord running to fridge in employee break room. Replace with a fused powerstrip. 4. Remove extension cord running overhead, in second floor loading dock. 5. Remove extension cord, by second floor dock office. |
12/29/2006 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. 1. Remove plastic lodged through ceiling tile in PLS room {first floor}. 2. Replace ceiling tile, in east hallway of loss prevention offices. 3. Replace ceiling tile, in second floor Men's shoe stock room. 4. Repair hole in wall, in second floor dinner ware stock room. 5. Replace ceiling tile, in second floor childrens stock room corridor. |
12/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defected. 1. Fire extinguishers shall be serviced annually and shall have a current service tag attached. {first floor electric room by petite department}. 2.Extinguisher shall be permanently mounted, in electrical room by elevator service room {first floor}. 3. Service and tag extinguisher in first floor electrical room, near sign room. 4. Service, mount, and tag extinguisher in second floor electrical room, by loading dock. 5. Service and tag extinguisher in chiller room, on roof. 6. The sprinkler system shall be serviced and tested. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02954
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2006 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |