Case: T06FR02954

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T06FR02954

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/29/2006 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
1. Sprinkler head obstructed in first floor dress stock room. Sprinkler heads shall be no less than 18 inches from storage.
2. Sprinkler heads shall not be obstructed. Remove shelves from obstructing sprinkler heads in second floor package check room.
3. Sprinkler heads shall not be obstructed. Remove storage from sprinkler head, in east hallway of loss prevention offices.
4. Sprinkler heads shall not be obstructed. Remove top level of storage rack in second floor Men's shoe dept.
5. Sprinkler heads shall not be obstructed. Remove top level of storage rack in second floor office supply room.
12/29/2006 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.
1. Remove storage from elevator service room {first floor}.
2. Remove storage from electrical room, by the elevator service room {first floor}.
3. Remove storage from first floor elevator electrical room.
4. Remove storage from electrical room, in second floor loading dock.
5. Remove storage from electrical room, by second floor men's dept.
6. Remove storage from electrical room, second floor west of elevator.
12/29/2006 VIOL - PRECAUTION AGAINST FIRE Correction Required TFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
1. Storage around, and on top of flamable liquids cabinet shall be removed. {first floor visual room}.