Case: T06FR02954

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR02954

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/02/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters “FDC” at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official.
1. The FDC on the north side of the building shall be visible to approaching fire apparatus. Mount a sign on the wall with an arrow indicating the location of the FDC.
12/29/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defected.
1. Fire extinguishers shall be serviced annually and shall have a current service tag attached. {first floor electric room by petite department}.
2.Extinguisher shall be permanently mounted, in electrical room by elevator service room {first floor}.
3. Service and tag extinguisher in first floor electrical room, near sign room.
4. Service, mount, and tag extinguisher in second floor electrical room, by loading dock.
5. Service and tag extinguisher in chiller room, on roof.
6. The sprinkler system shall be serviced and tested.