Case: T06FR02919
Case Details
Entered Date:
12/20/2006
Applicant:
FREIJ ELIAS Y & OBDULIA M CP/RS
Description:
Full Fire Inspection, Checklist used
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02919
Case Description: INSPECTION
Total Completed Inspections - 24
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | |
| 12/27/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | IFC 2003 1026.5 Emergecy ligting. EMERGENCY LIGHTING MUST BE HARD WIRE TO THE HOMES POWWER SOURCE. |
| 12/27/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | IFC 2003 1027.2 Must be able to use easily and reliable Check if they open and look at security devices. 1. REPAIR WINDOWS THAT DO NOT OPEN IN BEDROOMS 1 & 3 |
| 12/27/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | IFC 2003 1027.3 Egress pathway clear All path ways to all exits required or not. This includes exits from windows. 1. MOVE BED IN BEDROOM # 3 AWAY FROM WINDOW. |
| 12/27/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | IFC 2003 1027.2 Maintenance of egress components. 1. DOOR LEADING TO BACK YARD FROM E BATHROOM IS NOT AN EXIT , BUT A POOL DOOR. |
| 12/27/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | IFC 2003 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks. 1. REMOVE DOUBLD KEYED DEAD BOLT FROM WEST BEDROOM AND DISABLE THROW IN SECOND THUMB LATCH DEAD BOLT ON POOL DOOR AND FRONT EXIT. |
| 12/27/2006 | VIOL - FIRE RESIST.RATED CONST | SHIGGINB | Approved | |
| 12/27/2006 | VIOL - FIRE RESIST.RATED CONST | SHIGGINB | Approved | IFC 2003 703.1Must be repair w/ fire resistive materials Look behind washers and dryers, hot water heaters, heater closets. 1. REPAIR CEILING IN HEATER CLOSET |
| 12/27/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | |
| 12/27/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | SPRINKLER ARE NOT REQUIERED IN THE CLOSETS IN THE OFFICE AND BEDROOM #1, AS LONG AS NO DOOR IS PLACE ON CLOSET OPENNINGS. |
| 12/27/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | IFC 2003 907.2.10 Smoke alarms Check for operation and location. Min. is bedrooms and hallway. 1. REPAIR SMOKE ALARM IN LAUNTRY ROOM |
| 12/27/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | IFC 2003 903.2.10 All new Group R Occ. except Groups R-3 An automatic sprinkler system shall be installed in the locations set forth in Sections 903.2.10.1 through 903.2.10.1.3. R4 w/ new C/O requires sprinklers. 1. NO SPRINKLER HEAD IN HEATER CLOSET. REQUIERES A NEW FLOOR PLAN AND PERMIT. |
| 12/27/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | IFC 2003 901.6.2 Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. 1. MUST HAVE COPY OF FIRE ALARM TESTING ON SITE. |
| 12/27/2006 | VIOL - EMERGENCY PLAN/PREPARE | SHIGGINB | Approved | |
| 12/27/2006 | VIOL - EMERGENCY PLAN/PREPARE | SHIGGINB | Approved | IFC 2003 404.3.2 Emergency evacuation floor plan. This will include primary and secondary exits, extinguishers. TFC 408 has occupancy-related requirements. 1. MAP OF ESCAPE ROUGHTS MUST UPDATED. |
| 12/27/2006 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | |
| 12/27/2006 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | IFC 2003 TFC 603.1 & 316.2 Fuel fired appliances and house cleaning. Furnaces, dryer and hot water heaters are all heat sources and must be maintained and cleaned. 1. CLEAN AROUND DRYER AND CHECK FOR A LEAK IN VENT TUBE. |
| 12/27/2006 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | IFC 2003 307 BBQ 10’ from combustibles BBQ must be used 10’ from combustibles. Gas BBQs must stored 10’ away from combustibles 1. BRICK BBQ TO CLOSE TO BUILDING. REMOVE OR HAVE A HOOD SYSYTEM PUT IN. |
| 12/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | |
| 12/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | IFC 2003 604.4 Fuel type portable heater ( prohibited ) Electrical heaters should have a tip switch. 1. PORTABLE HEATERS SHOULD HAVE A TIP SHUT-OFF |
| 12/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | IFC 2003 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/ power strip that has overcurrent protection 1. SURGED POWER TAP IS DAMAGED, REMOVE AND REPLACE WITH NEW POWER TAP. |
| 12/27/2006 | VIOL - ADMINISTRATION | SHIGGINB | Approved | |
| 12/27/2006 | VIOL - ADMINISTRATION | SHIGGINB | Approved | IFC 2003 102.3 Change of use of a building Must have it posted, must have correct occupancy type, and licensed amount must match occupancy class. 1. NEED A C OF O AND IT MUST BE POSTED |
| 12/27/2006 | INSP - FULL | SHIGGINB | Approved |