Case: T06FR02919

Parcel: 127070450


Addresses:

5120 E ALBERTA DR

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
12/27/2006 VIOL - MEANS OF EGRESS Violation IFC 2003 1008.18 Door operation
No double key dead-bolt locks, no special knowledge needed,
no slide bolt locks.
1. REMOVE DOUBLD KEYED DEAD BOLT FROM WEST BEDROOM AND DISABLE THROW IN SECOND THUMB LATCH DEAD BOLT ON POOL DOOR AND FRONT EXIT.
12/27/2006 VIOL - MEANS OF EGRESS Violation IFC 2003 1027.2 Maintenance of egress components.
1. DOOR LEADING TO BACK YARD FROM E BATHROOM IS NOT AN EXIT , BUT A POOL DOOR.
12/27/2006 VIOL - MEANS OF EGRESS Violation IFC 2003 1027.3 Egress pathway clear
All path ways to all exits required or not. This includes exits from
windows.
1. MOVE BED IN BEDROOM # 3 AWAY FROM WINDOW.
12/27/2006 VIOL - MEANS OF EGRESS Violation IFC 2003 1027.2 Must be able to use easily and reliable
Check if they open and look at security devices.
1. REPAIR WINDOWS THAT DO NOT OPEN IN BEDROOMS 1 & 3
12/27/2006 VIOL - MEANS OF EGRESS Violation IFC 2003 1026.5 Emergecy ligting.
EMERGENCY LIGHTING MUST BE HARD WIRE TO THE HOMES POWWER SOURCE.
12/27/2006 VIOL - MEANS OF EGRESS Approved