Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/13/2006

Applicant:

4-D PROPERTIES

Description:

Occupancy Type: A-2 C of O: Please provide a copy of your Certificate of Occupancy [C of O] upon re-inspection. Business Name: Philly's Finest Property Representative: Mitch Bart, Owner/Manager, 400-3226c Full Inspection Completed: 12/12/06 Re-Inspection Date: 12/29/06 Next re-inspection date on or after: 1/12/07 If you have any questions please call me at 791-4502 ____________________________________________________________ David Greenleaf, Inspector, Tucson Fire Department _______________________I have received a copy of this inspection report. Building Representative _______________________ Captain

Outstanding Inspections

Case Number: T06FR02880
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/14/2006 VIOL - MEANS OF EGRESS DGREENLE Correction Required Emergency lighting not working 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise’s electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. ***Repair or replace emergency lights in back hall
12/14/2006 VIOL - MEANS OF EGRESS DGREENLE Correction Required Exit sign over front door not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. ***Fix light in exit sign.
12/14/2006 VIOL - MEANS OF EGRESS DGREENLE Correction Required Exit sign over rear door not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. ***Fix light in exit sign.
12/14/2006 VIOL - MEANS OF EGRESS DGREENLE Correction Required Razor wire hanging outside rear door: 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. ***Secure razor wire out of reach or remove it.
12/15/2006 VIOL - FIRE SERVICE FEATURES DGREENLE Correction Required TFC 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. ***Mark rear door as blocked.
12/15/2006 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required Extension cord through ceiling tile: TFC 605.5 Extension cords. ...Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors... ***Remove extension cord in kitchen and/or replace with approved permanent electrical power source.
12/15/2006 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. *** Replace extension cord in office with approved power strip.
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required Extinguishers not inspected / tagged: TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ***1. Extinguishers shall be inspected and tagged in accordance with this code.
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required Grease accumulation in hood system. 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ***the hood system shall be cleaned.
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required Hood system not inspected / tagged: 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ***The hood exhaust and extinguishing systems shall be inspected and tagged.
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required Training in use of hood system manual activation: 904.11 Commercial cooking systems. ***Employees working in the kitchen shall know the location of the pull station and how to use it to manually activate the fire supression system. The system shall be clearly labled.
12/29/2006 INSP - REINSPECTION DGREENLE Continued re-inspection 12/29/06. No evidence of any work completed. Mitch Bart out of town for holiday. Set re-inspection date for 1/12/07

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02880
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/02/2007 COMPL - REINSPECTION DGREENLE Approved