Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T06FR02880

Parcel: 12710084B


Addresses:

6210 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR02880

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required Extinguishers not inspected / tagged:
TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
***1. Extinguishers shall be inspected and tagged in accordance with this code.
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required Hood system not inspected / tagged:
904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.
***The hood exhaust and extinguishing systems shall be inspected and tagged.
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required Grease accumulation in hood system.
904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
***the hood system shall be cleaned.
12/15/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required Training in use of hood system manual activation:
904.11 Commercial cooking systems.
***Employees working in the kitchen shall know the location of the pull station and how to use it to manually activate the fire supression system. The system shall be clearly labled.