Case: T06FR02794
Case Details
Entered Date:
11/29/2006
Applicant:
TARGET CORPORATION
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR02794
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2006 | VIOL - PRECAUTION AGAINST FIRE | JDAVIS | Correction Required | 315.2.1 -Combustible Stock shall be orderly - Maintain aisle width in stock rooms throughout the store |
11/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | JDAVIS | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. -Repair the exposed wires inte Garden Center (North wall). |
11/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | JDAVIS | Correction Required | 605.5 Do not use extension cords as a substitute for permanent wiring: -SE exit going through the door |
11/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | JDAVIS | Correction Required | Electronic Stock Room: 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. - Remove the stock that is against the panel -Pharmacy |
11/29/2006 | VIOL - FIRE RESIST.RATED CONST | JDAVIS | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained... -Repair the breach in the ceiling in the photo shop storage room |
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | JDAVIS | Correction Required | |
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | JDAVIS | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. - Stock shall not come within 18 or sprinkler heads or piping 1. Photo 2. Pharmacy |
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | JDAVIS | Correction Required | 901.4 Sprinkler system shall be extended to maintain coverage: -Rear Electrical room |
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | JDAVIS | Correction Required | 901.4 Do not hinder the normal operation of the sprinkler system: -Building services |
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | JDAVIS | Correction Required | 901.6 Fire extinguishers shall be serviced annually: -Seasonal stock area |
11/29/2006 | VIOL - MEANS OF EGRESS | JDAVIS | Correction Required | 1003.6 Do not block exits with stock: -the SE exit currently has boxes stored outside which blockes the egress path. |
11/29/2006 | VIOL - MEANS OF EGRESS | JDAVIS | Correction Required | 1008.8.9 #2 Panic hardware shall be openable from the inside when less than 15 pounds of force is applied to the egress side. -Rear exit from main stock room |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02794
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2006 | INSP - FULL | JDAVIS | Approved |