Case: T06FR02794

Parcel: 13355231B

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR02794

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/29/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required Electronic Stock Room:
605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
- Remove the stock that is against the panel
-Pharmacy
11/29/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.
-Repair the exposed wires inte Garden Center (North wall).
11/29/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5
Do not use extension cords as a substitute for permanent wiring:
-SE exit going through the door