Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR02794
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Electronic Stock Room: 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. - Remove the stock that is against the panel -Pharmacy |
|
11/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. -Repair the exposed wires inte Garden Center (North wall). |
|
11/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.5 Do not use extension cords as a substitute for permanent wiring: -SE exit going through the door |