Case: T06FR02794

Parcel: 13355231B

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR02794

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/29/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
- Stock shall not come within 18 or sprinkler heads or piping
1. Photo
2. Pharmacy
11/29/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.4
Sprinkler system shall be extended to maintain coverage:
-Rear Electrical room
11/29/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Fire extinguishers shall be serviced annually:
-Seasonal stock area
11/29/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.4 Do not hinder the normal operation of the sprinkler system:
-Building services
11/29/2006 VIOL - FIRE PROTECTION SYSTEMS Correction Required