Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T06FR02794
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. - Stock shall not come within 18 or sprinkler heads or piping 1. Photo 2. Pharmacy |
|
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 901.4 Sprinkler system shall be extended to maintain coverage: -Rear Electrical room |
|
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 901.6 Fire extinguishers shall be serviced annually: -Seasonal stock area |
|
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 901.4 Do not hinder the normal operation of the sprinkler system: -Building services |
|
11/29/2006 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required |