Case: T06FR02632
Case Details
Entered Date:
10/03/2006
Applicant:
LCC-PANTANO/GOLF LINKS LLC
Description:
FULL INSPECTION
Outstanding Inspections
Case Number: T06FR02632
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
10/03/2006 | VIOL - PRECAUTION AGAINST FIRE | JDAVIS | Correction Required | 1. 315.2.2 Means of egress. Combustible materials shall not be stored in exits or exit enclosures. - Remove the storage that is in the East exit way. 2. 315.2.4 Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 1.75 inches (44.5 mm) in thickness. Storage shall not be placed on exposed joists. -Do not store files in your attic space above the coolers |
10/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | JDAVIS | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. -Currently the outlet near the garbage containers out side is broken. Re-inspection Date: October3, 2006 Property Representative Signature: __________________________ Inspector: ____________________________________ Date Approved: ______/______/_____ Captian Signature: ___________________________ |
10/03/2006 | VIOL - FIRE PROTECTION SYSTEMS | JDAVIS | Correction Required | 901.7/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Fire estingiushers shall be properly mounted and serviced annually. -Front counter |
10/03/2006 | VIOL - MEANS OF EGRESS | JDAVIS | Correction Required | MEANS OF EGRESS ILLUMINATION 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. CURRENTLY THERE ARE 4 EXIT SIGNS WHICH NEED ILLUMINATION |
10/03/2006 | VIOL - MOTOR FUEL DISPENSING | JDAVIS | Correction Required | 1. DISPENSING OPERATIONS 2204.1 Supervision of dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be conducted by a qualified attendant or shall be under the supervision of a qualified attendant at all times or shall be in accordance with Section: -Train your employees about the emergency fuel shut-off systems. 2. 2203.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations. -Provide signs for your e-stops ( 2ea.) -Ensure that the e-stposd are operational 3. 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times in accordance with Sections 2205.2.1 through 2205.2.3. A. Pump #3 87 cotane--leaking from swivel B. Pump #7 87 Octane--upper hose assembly needs replacing |
10/03/2006 | VIOL - COMPRESSED GASES | JDAVIS | Correction Required | 3003.3 Security. Compressed gas containers, cylinders, and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in with Sections 3003.3.1 through 3003.3.3. -Properly secure all compressed gas cylinders |
10/20/2006 | VIOL - ADMINISTRATION | JDAVIS | Correction Required | Pre-citation letter sent. Contents below: PRE-CITATION LETTER 10/20/06 CATALINA MART ATTN: ROBERT MAHLSTED LCC-PANTANO/ GOLFLINKS LLC 3610 N. PRINCE VIIAGE PL. STE 100 TUCSON, AZ. 85719 RE: FIRE INSPECTION: 7910 E. GOLFLINKS Dear Mr. Mahlsted, The Tucson Fire Department has conducted a fire safety inspections at the above stated business on September 29, 2006. At that time a notice was issued indicating the corrections required to provide compliance with the applicable codes, regulations and ordinances. A Subsequent re-inspection was conducted on Oct. 13, 2006. One item was corrected. We were unable to gain voluntary compliance. Compliance is required by the 2003 Uniform Fire Code w/ Modifications MEANS OF EGRESS ILLUMINATION 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. § CURRENTLY THERE ARE 4 EXIT SIGNS WHICH NEED ILLUMINATION MEANS OF EGRESS 315.2.2 Combustible materials shall not be stored in exits or exit enclosures. § Remove the storage that is in the East exit way. ATTIC, UNDER-FLOOR AND CONCEALED SPACES. 315.2.4 Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. § Do not store files in your attic space above the coolers INSPECTION, TESTING AND MAINTENANCE 901.7/ 901.6 Fire extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.. Fire extinguishers shall be properly mounted and serviced annually. § Front counter DISPENSING OPERATIONS 2204.1 Supervision of dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be conducted by a qualified attendant or shall be under the supervision of a qualified attendant at all times or shall be in accordance with Section: § Train your employees about the emergency fuel shut-off systems. EMERGENCY DISCONNECT SWITCHES 2203.2 An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations: § Provide signs for your e-stops ( 2ea.) EQUIPMENT MAINTENANCE AND INSPECTION. 2205.2 Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times in accordance with Sections 2205.2.1 through 2205.2.3. § Pump #3 87 Octane--leaking from swivel § Pump #7 87 Octane--upper hose assembly needs replacing SECURITY-COMPRESSED GAS CYILNDER 3003.3 Compressed gas containers, cylinders, and systems shall be secured against accidental dislodgment. § Properly secure all compressed gas cylinders ABATEMENT OF ELECTRICAL HAZARDS. 605.1 Identified electrical hazards shall be abated. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. § Currently the outlet near the garbage containers out side is broken. This letter is to inform you that if the above stated necessary corrections have not been completed November 3, 2006 a citation will be issued which will require an appearance by you in court with a probable fine. This letter is written as a courtesy to you in order to avoid future litigation. Sincerely, Jimmy R. Davis, Jr. Fire Inspector Tucson Fire Department |