Case: T06FR02632

Parcel: 136153850

Inspection Status: Correction Required

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T06FR02632

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/03/2006 VIOL - MOTOR FUEL DISPENSING Correction Required 1. DISPENSING OPERATIONS
2204.1 Supervision of dispensing. The dispensing of fuel at
motor fuel-dispensing facilities shall be conducted by a qualified
attendant or shall be under the supervision of a qualified attendant
at all times or shall be in accordance with Section:

-Train your employees about the emergency fuel shut-off systems.

2. 2203.2 Emergency disconnect switches. An approved,
clearly identified and readily accessible emergency disconnect
switch shall be provided at an approved location, to stop the
transfer of fuel to the fuel dispensers in the event of a fuel spill
other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.

-Provide signs for your e-stops ( 2ea.)
-Ensure that the e-stposd are operational

3. 2205.2 Equipment maintenance and inspection. Motor
fuel-dispensing facility equipment shall be maintained in
proper working order at all times in accordance with Sections
2205.2.1 through 2205.2.3.
A. Pump #3 87 cotane--leaking from swivel
B. Pump #7 87 Octane--upper hose assembly needs replacing