Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/23/2006

Applicant:

PIMA COUNTY

Description:

this is a museum that is requesting a fire inspection to satisfy some state requirements. He would like to have it performed by the end of august. The business hours are m-f- 8:30 am to 4:30 pm. he stated that any day would be fine but asked for a courtesy call prior to arrival.

Outstanding Inspections

Case Number: T06FR02484
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/28/2006 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation IFC 315.2- Storage of combustibles shall be separated from heating devices by distance or shielding so that ignition cannot occur. 1. Storage room- plastic near light fixture.
08/28/2006 VIOL - FIRE SERVICE FEATURES JLANGEJA Violation IFC 504.2- Exterior doors that have been rendered non-functional shall have the words "THIS DOOR BLOCKED". The letters shall be a minimum of 6" high, 3/4" wide on a contrasting background. (N side)
08/28/2006 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation IFC 605.1- Identified electrical hazards shall be abated. 1. (outside) E wall receptacle shall be weather resistant. 2. (outside) E wall main circuit panel plate shall be secured. 3. (closet) N of showroom, wires shall be protected per NEC. 4. (closet) W of showroom, wires shall be protected per NEC.
08/28/2006 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation IFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. (research) ext. cord to laser printer. 2. (bombing display) ext. cord on E wall of showroom. 3. (upstairs) ext. cord to overhead lights.
08/28/2006 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation IFC 605.6- Open junction boxes shall be prohibited. (closet) N of showroom, open junction box shall be covered.
08/28/2006 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation IFC 901.6- Fire extinguishers shall be serviced annually. 1. Research room 2. Library 3. 95th room (H) N wall 4. Storage room (H) 5. Maintenance room (H) 6. Show room (H) N wall 7. Show room (H) W wall 8. Show room, missing, S wall 9. Upstairs (H) 10. Smoke detector shall be replaced.
08/28/2006 VIOL - MEANS OF EGRESS JLANGEJA Violation IFC 1003.6- The path of egress travel shall not be interrupted. 1. Research room exit is blocked. 2. Foyer (outside) remove chain. 3. Foyer (inside) remove signs preventing access to outside. 4. Upstairs pathways 5. Library- remove "NO EXIT" sign from W door.
08/28/2006 VIOL - MEANS OF EGRESS JLANGEJA Violation IFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. 1. Research room 2. 95th room 3. Storage room 4. Maintenance room 5. Show room (W wall)
08/28/2006 VIOL - MEANS OF EGRESS JLANGEJA Violation IFC 1011.2- Exit signs shall be internally or externally illuminated. 1. Research room (E wall) remove sign on W side. 2. Library (W wall) remove sign on E wall. 3. Show room (W wall)
08/28/2006 VIOL - MEANS OF EGRESS JLANGEJA Violation IFC 1011.5.3- Exit signs shall be illuminated at all times. 1. Research room (E wall) 2. Library (W wall) 3. Show room (W wall)
08/28/2006 VIOL - MEANS OF EGRESS JLANGEJA Violation IFC 1027.6- Where panic hardware is installed, it shall be the on locking device on the door. 1. Research room 2. 95th room 3. Storage room 4. Maintenance room 5. Show room (W wall)

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02484
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/18/2006 INSP - REINSPECTION JLANGEJA Approved All violations have been corrected.