Case: T06FR02484

Parcel: 140360120


Addresses:

6000 E VALENCIA RD


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR02484

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
08/28/2006 VIOL - MEANS OF EGRESS Violation IFC 1027.6- Where panic hardware is installed, it shall be the on locking device on the door.
1. Research room
2. 95th room
3. Storage room
4. Maintenance room
5. Show room (W wall)
08/28/2006 VIOL - MEANS OF EGRESS Violation IFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted.
1. Research room
2. 95th room
3. Storage room
4. Maintenance room
5. Show room (W wall)
08/28/2006 VIOL - MEANS OF EGRESS Violation IFC 1003.6- The path of egress travel shall not be interrupted.
1. Research room exit is blocked.
2. Foyer (outside) remove chain.
3. Foyer (inside) remove signs preventing access to outside.
4. Upstairs pathways
5. Library- remove "NO EXIT" sign from W door.
08/28/2006 VIOL - MEANS OF EGRESS Violation IFC 1011.2- Exit signs shall be internally or externally illuminated.
1. Research room (E wall) remove sign on W side.
2. Library (W wall) remove sign on E wall.
3. Show room (W wall)
08/28/2006 VIOL - MEANS OF EGRESS Violation IFC 1011.5.3- Exit signs shall be illuminated at all times.
1. Research room (E wall)
2. Library (W wall)
3. Show room (W wall)