Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2006 | VIOL - MEANS OF EGRESS | Violation | IFC 1027.6- Where panic hardware is installed, it shall be the on locking device on the door. 1. Research room 2. 95th room 3. Storage room 4. Maintenance room 5. Show room (W wall) |
|
| 08/28/2006 | VIOL - MEANS OF EGRESS | Violation | IFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. 1. Research room 2. 95th room 3. Storage room 4. Maintenance room 5. Show room (W wall) |
|
| 08/28/2006 | VIOL - MEANS OF EGRESS | Violation | IFC 1003.6- The path of egress travel shall not be interrupted. 1. Research room exit is blocked. 2. Foyer (outside) remove chain. 3. Foyer (inside) remove signs preventing access to outside. 4. Upstairs pathways 5. Library- remove "NO EXIT" sign from W door. |
|
| 08/28/2006 | VIOL - MEANS OF EGRESS | Violation | IFC 1011.2- Exit signs shall be internally or externally illuminated. 1. Research room (E wall) remove sign on W side. 2. Library (W wall) remove sign on E wall. 3. Show room (W wall) |
|
| 08/28/2006 | VIOL - MEANS OF EGRESS | Violation | IFC 1011.5.3- Exit signs shall be illuminated at all times. 1. Research room (E wall) 2. Library (W wall) 3. Show room (W wall) |