Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

REFERRED

Type:

INSPECTION
Address:

Entered Date:

05/03/2006

Applicant:

KELLEY MARGARET 1/2 & KELLEY T A JR &

Description:

Full Inspection

Outstanding Inspections

Case Number: T06FR01140
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 16
End Date Description Inspector Results Comments
04/25/2006 VIOL - ADMINISTRATION NSPRENGE Violation 1. IFC 2003 102.3 The provisions of the International Building Code shall apply to buildings undergoing a change of occupancy. Acquire a certificate of occupancy for this address. Contact Developmental Services Department at ( 791-5550).
04/25/2006 VIOL - ADMINISTRATION NSPRENGE Violation 2. IFC 2003 102.4 Repairs, alterations and additions to existing structures shall comply with the International Building Code or the New Jersey Rehabilitation Sub-code. There have been many alterations to this building including breaching walls and walling ogg doors. This address will be refered to DSD. Contact DSD at 791-5550 to obtain a building inspection.
04/25/2006 VIOL - PRECAUTION AGAINST FIRE NSPRENGE Violation IFC 2003 315.2 Storage of combustible materials in buildings shall be orderly. Storage in shop must be organized and removal of empty boxes/containers will reduce fuel load. Clean up NW corner storage addition.
04/25/2006 VIOL - PRECAUTION AGAINST FIRE NSPRENGE Violation IFC 2003 315.2.1 Maintain 2 feet space between ceiling and combustible storage in storage room ( NW corner addition.)
04/25/2006 VIOL - PRECAUTION AGAINST FIRE NSPRENGE Violation IFC 2003 315.2.2 Combustible materials shall not be stored in exits. Remove boxes blocking egress from storage area and maintain 36 inch isles.
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 1. IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove 2 cords in Realty Office.
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 2. IFC 2003 605.3 Provide 30 inches width, 36 inches depth, and 78 inches in height in front of electrical service equipment. Remove objects blocking clearance.
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 3. IFC 2003 603.7 STOP OPERATION OF DRYERS IN LAUNDRY MAT UNTIL A MECHANICAL INSPECTOR INSPECTS THE MECHANICAL ROOMS BEHIND THE DRYERS. STOP OPERATION OF BOILERS IN THOSE ROOMS. Contact the Department of Neighborhood Resources to arrange mechanical Inspections ( 791 - 4605 )
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 4. IFC 2003 605.6 Open wiring splices are prohibited. Install junction boxes to cover open wiring in the laundry mat ceiling area and behind dryers on South end. Place covers on 1 open outlet, and 2 open light switches in upstairs apartment.
04/25/2006 VIOL - FIRE RESIST.RATED CONST NSPRENGE Violation 1. IFC 2003 703.1 Fire resistive reting of fire resistant construction shall be maintained. Replace ceiling in laundry area and in rooms behind laundry mat that lead to the dryer mechanical areas.
04/25/2006 VIOL - FIRE RESIST.RATED CONST NSPRENGE Violation 2. IFC 2003 703.1 Maintain fire resistive rating. Have building inspector assess breaks in walls between the shop and the laundry area for seperation requirement.
04/25/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1. IFC 2003 1011.1 Exits shall be marked with an approved exit sign visible from all directions of travel. Install proper exit signs pending C of O from DSD.
04/25/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 2. IFC 2003 1017.2.2 Exterior exit doors shall lead to a public way. South lot must be opened to a public way if laundry area is to be in use in future, pending building inspection/mechanical/ electrical.
04/25/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 3. IFC 2003 1008.1.8.4 Manually operated flush bolts or surface bolts are not permitted. Remove 2 slide bolt locks from exit in mechanical room housing the boilers.
04/25/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 4. IFC 2003 1008.1.8.3 Doors from individual dwelling units must be openable from egress side with out the use of a key or tool. Install hand turning dead bolt on egress side of security gate at the bottom of the stairs.
05/03/2006 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation 1. IFC 2003 906.2 Fire extinguishers shall be installed and maintained in accordance with this section and NFPA 10. Service fire extinguisher in shop area.

Completed Inspections

Case Status: REFERRED
Case Number: T06FR01140
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/21/2006 INSP - REINSPECTION NSPRENGE Approved All hazards abated and building is approved.
09/25/2009 INSP - FULL NSPRENGE Approved

Outstanding Case Activity Conditions

Date Name Approved
05/03/2006 Referred to Developmental Services for C of O Not Approved