Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/25/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
1. IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove 2 cords in Realty Office. |
| 04/25/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
2. IFC 2003 605.3 Provide 30 inches width, 36 inches depth, and 78 inches in height in front of electrical service equipment. Remove objects blocking clearance. |
| 04/25/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
3. IFC 2003 603.7 STOP OPERATION OF DRYERS IN LAUNDRY MAT UNTIL A MECHANICAL INSPECTOR INSPECTS THE MECHANICAL ROOMS BEHIND THE DRYERS. STOP OPERATION OF BOILERS IN THOSE ROOMS. Contact the Department of Neighborhood Resources to arrange mechanical Inspections ( 791 - 4605 ) |
| 04/25/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
4. IFC 2003 605.6 Open wiring splices are prohibited. Install junction boxes to cover open wiring in the laundry mat ceiling area and behind dryers on South end. Place covers on 1 open outlet, and 2 open light switches in upstairs apartment. |