Case: T06FR01140

Parcel: 10406013A


Addresses:

4049 N ROMERO RD

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 1. IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove 2 cords in Realty Office.
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 2. IFC 2003 605.3 Provide 30 inches width, 36 inches depth, and 78 inches in height in front of electrical service equipment. Remove objects blocking clearance.
04/25/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 3. IFC 2003 603.7 STOP OPERATION OF DRYERS IN LAUNDRY MAT UNTIL A MECHANICAL INSPECTOR INSPECTS THE MECHANICAL ROOMS BEHIND THE DRYERS. STOP OPERATION OF BOILERS IN THOSE ROOMS. Contact the Department of Neighborhood Resources to arrange mechanical Inspections ( 791 - 4605 )