Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/25/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
1. IFC 2003 1011.1 Exits shall be marked with an approved exit sign visible from all directions of travel. Install proper exit signs pending C of O from DSD. |
| 04/25/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
2. IFC 2003 1017.2.2 Exterior exit doors shall lead to a public way. South lot must be opened to a public way if laundry area is to be in use in future, pending building inspection/mechanical/ electrical. |
| 04/25/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
3. IFC 2003 1008.1.8.4 Manually operated flush bolts or surface bolts are not permitted. Remove 2 slide bolt locks from exit in mechanical room housing the boilers. |
| 04/25/2006 |
VIOL - MEANS OF EGRESS |
|
Violation |
4. IFC 2003 1008.1.8.3 Doors from individual dwelling units must be openable from egress side with out the use of a key or tool. Install hand turning dead bolt on egress side of security gate at the bottom of the stairs. |