Case: T06FR00265
Case Details
Entered Date:
03/03/2006
Applicant:
CAID T A & SONS INC GENERAL SHEET METAL
Description:
Would like inspector to go out and make sure everthing is up to code please contact Glenn Henderson at 294-7311
Outstanding Inspections
Case Number: T06FR00265
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 16
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2006 | INSP - FULL | RSUMMER | Correction Required | jvalenz1 assigned. |
| 03/14/2006 | VIOL - FIRE SERVICE FEATURES | JVALENZU | Violation | 505.1 - address numbers shall be placed onthe building in a position that is plainly visible from the street fronting the property. |
| 03/14/2006 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Violation | · TFC 605.3 - a working space of not less than 30"Wx36"Dx78"H shall be provided in front of electrical service equipment. This condition occurs in various locations throughout the shop |
| 03/14/2006 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Violation | · TFC 605.5 - extension cords shall not be used as a substitute for permanent wiring. Although many were removed during the inspection, this was a very common occurrence that will require much attention |
| 03/14/2006 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Violation | · TFC 605.6 - open junction boxes and open-wiring splices shall be prohibited. A cover is needed on a receptacle box outside on the south porch |
| 03/14/2006 | VIOL - FIRE PROTECTION SYSTEMS | JVALENZU | Violation | · TFC 901.6 - fire protection systems shall be maintained in an operative condition at all times. The FDC shall be maintained per NFPA requirements |
| 03/14/2006 | VIOL - MEANS OF EGRESS | JVALENZU | Violation | · TFC 1003.6 - obstructions shall not be placed in the required width of means of egress. Materials and equipment obstructed both exit paths from the work areas on the east side of the shop |
| 03/14/2006 | VIOL - MEANS OF EGRESS | JVALENZU | Violation | · TFC 1008.1.8 - egress doors shall be readily openable from the inside without the use of a key or special knowledge or effort; the unlatching of any leaf shall not require more than one operation. The exit doors shall only have one lock per door. |
| 03/14/2006 | VIOL - MEANS OF EGRESS | JVALENZU | Violation | · TFC 1011.1 - exits and exit access doors shall be marked by an approved illuminated exit sign readily visible from any direction of egress travel. Signs are required from the work areas on the east side of the shop. |
| 03/14/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JVALENZU | Violation | · TFC 2703.1.1(1) - the maximum allowable quantity of flammable gas in use and storage shall be 2000 cubic feet inside the building. This is to include the hydrogen gas and propane gas. |
| 03/14/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JVALENZU | Violation | · TFC 2703.5.1 - individual containers shall be conspicuously marked or labeled in an approved manner. 55-gallon drums containing coolant, inside and outside shall be labeled. |
| 03/14/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JVALENZU | Violation | · TFC 2703.8.7 - hazardous materials storage cabinets shall be constructed with self-closing and self-latching doors. The outside wash area cabinet in non-compliant. |
| 03/14/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JVALENZU | Violation | · TFC 2703.9.3 - guard posts or other approved means shall be provided to protect piping valves and fittings. The natural gas supply line outside the east wall shall be protected. |
| 03/14/2006 | VIOL - COMPRESSED GASES | JVALENZU | Violation | · TFC 3003.2 - compressed gas cylinders systems shall be marked with the name of the gas. The storage rack in the southeast corner. |
| 03/14/2006 | VIOL - COMPRESSED GASES | JVALENZU | Violation | · TFC 3003.3.3 - compressed gas cylinders shall be secured to prevent falling. A hydrogen cylinder in the southeast corner. |
| 03/14/2006 | VIOL - FLAMMABLE LIQUIDS | JVALENZU | Violation | · TFC 3405.3.6.2 - parts cleaning machine shall be conducted in a listed machine in accordance with their listing · Solvent shall be compatible with the machine · Machines shall be adequately ventilated · Installed per manufacturers instructions · Serviced and maintained per manufacturers instructions including electrical wiring components and fire safety features. |