Outstanding Inspections

Case Number: T06FR00265
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 16
End Date Description Inspector Results Comments
03/03/2006 INSP - FULL RSUMMER Correction Required jvalenz1 assigned.
03/14/2006 VIOL - FIRE SERVICE FEATURES JVALENZU Violation 505.1 - address numbers shall be placed onthe building in a position that is plainly visible from the street fronting the property.
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 605.3 - a working space of not less than 30"Wx36"Dx78"H shall be provided in front of electrical service equipment. This condition occurs in various locations throughout the shop
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 605.5 - extension cords shall not be used as a substitute for permanent wiring. Although many were removed during the inspection, this was a very common occurrence that will require much attention
03/14/2006 VIOL - BUILDING SVCS & SYSTEMS JVALENZU Violation · TFC 605.6 - open junction boxes and open-wiring splices shall be prohibited. A cover is needed on a receptacle box outside on the south porch
03/14/2006 VIOL - FIRE PROTECTION SYSTEMS JVALENZU Violation · TFC 901.6 - fire protection systems shall be maintained in an operative condition at all times. The FDC shall be maintained per NFPA requirements
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1003.6 - obstructions shall not be placed in the required width of means of egress. Materials and equipment obstructed both exit paths from the work areas on the east side of the shop
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1008.1.8 - egress doors shall be readily openable from the inside without the use of a key or special knowledge or effort; the unlatching of any leaf shall not require more than one operation. The exit doors shall only have one lock per door.
03/14/2006 VIOL - MEANS OF EGRESS JVALENZU Violation · TFC 1011.1 - exits and exit access doors shall be marked by an approved illuminated exit sign readily visible from any direction of egress travel. Signs are required from the work areas on the east side of the shop.
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN JVALENZU Violation · TFC 2703.1.1(1) - the maximum allowable quantity of flammable gas in use and storage shall be 2000 cubic feet inside the building. This is to include the hydrogen gas and propane gas.
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN JVALENZU Violation · TFC 2703.5.1 - individual containers shall be conspicuously marked or labeled in an approved manner. 55-gallon drums containing coolant, inside and outside shall be labeled.
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN JVALENZU Violation · TFC 2703.8.7 - hazardous materials storage cabinets shall be constructed with self-closing and self-latching doors. The outside wash area cabinet in non-compliant.
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN JVALENZU Violation · TFC 2703.9.3 - guard posts or other approved means shall be provided to protect piping valves and fittings. The natural gas supply line outside the east wall shall be protected.
03/14/2006 VIOL - COMPRESSED GASES JVALENZU Violation · TFC 3003.2 - compressed gas cylinders systems shall be marked with the name of the gas. The storage rack in the southeast corner.
03/14/2006 VIOL - COMPRESSED GASES JVALENZU Violation · TFC 3003.3.3 - compressed gas cylinders shall be secured to prevent falling. A hydrogen cylinder in the southeast corner.
03/14/2006 VIOL - FLAMMABLE LIQUIDS JVALENZU Violation · TFC 3405.3.6.2 - parts cleaning machine shall be conducted in a listed machine in accordance with their listing · Solvent shall be compatible with the machine · Machines shall be adequately ventilated · Installed per manufacturers instructions · Serviced and maintained per manufacturers instructions including electrical wiring components and fire safety features.