Case: T06FR00265

Parcel: 14028004B


Addresses:

2220 E BILBY RD

Inspection Status: Violation

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Date Description Inspector Results Comments
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN Violation · TFC 2703.8.7 - hazardous materials storage cabinets shall be constructed with self-closing and self-latching doors. The outside wash area cabinet in non-compliant.
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN Violation · TFC 2703.5.1 - individual containers shall be conspicuously marked or labeled in an approved manner. 55-gallon drums containing coolant, inside and outside shall be labeled.
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN Violation · TFC 2703.9.3 - guard posts or other approved means shall be provided to protect piping valves and fittings. The natural gas supply line outside the east wall shall be protected.
03/14/2006 VIOL - HAZARDOUS MATERIALS,GEN Violation · TFC 2703.1.1(1) - the maximum allowable quantity of flammable gas in use and storage shall be 2000 cubic feet inside the building. This is to include the hydrogen gas and propane gas.