Inspection Status: Violation
Inspection History: VIOL - HAZARDOUS MATERIALS,GEN
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2006 |
VIOL - HAZARDOUS MATERIALS,GEN |
|
Violation |
· TFC 2703.8.7 - hazardous materials storage cabinets shall be constructed with self-closing and self-latching doors. The outside wash area cabinet in non-compliant. |
| 03/14/2006 |
VIOL - HAZARDOUS MATERIALS,GEN |
|
Violation |
· TFC 2703.5.1 - individual containers shall be conspicuously marked or labeled in an approved manner. 55-gallon drums containing coolant, inside and outside shall be labeled. |
| 03/14/2006 |
VIOL - HAZARDOUS MATERIALS,GEN |
|
Violation |
· TFC 2703.9.3 - guard posts or other approved means shall be provided to protect piping valves and fittings. The natural gas supply line outside the east wall shall be protected. |
| 03/14/2006 |
VIOL - HAZARDOUS MATERIALS,GEN |
|
Violation |
· TFC 2703.1.1(1) - the maximum allowable quantity of flammable gas in use and storage shall be 2000 cubic feet inside the building. This is to include the hydrogen gas and propane gas. |