Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
· TFC 605.3 - a working space of not less than 30"Wx36"Dx78"H shall be provided in front of electrical service equipment. This condition occurs in various locations throughout the shop |
| 03/14/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
· TFC 605.5 - extension cords shall not be used as a substitute for permanent wiring. Although many were removed during the inspection, this was a very common occurrence that will require much attention |
| 03/14/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
· TFC 605.6 - open junction boxes and open-wiring splices shall be prohibited. A cover is needed on a receptacle box outside on the south porch |