Case: T06FR00053
Case Details
Entered Date:
01/17/2006
Applicant:
PUEBLO CENTER PARTNERS LTD PARTNERSHIP
Description:
inspection
Outstanding Inspections
Case Number: T06FR00053
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2006 | INSP - FULL | EGRIFFIN | Violation | 1). Basement- Holes in ceiling by galley area, laundry room, and small storage room, shall have ceilings tiles maintained. IFC 703. 2). Fire alarm test indicates that horns were not sounded during test. This shall be submitted to plans review for approval. IFC 901.6 3). Mech. Room. All J-Boxes shall be covered. IFC 605.1 4). Replace glass on standpipe cabinets in floor of parking garage. IFC 901.6 5). All doors with door closures shall be closed at all times. IFC 703.2.2. 6). Old trash shoot shall be cleaned out entirely and sealed. IFC 703.1 7). All combustibles shall be 30 inches from electrical panels. IFC 605.23 8). All caps, and lids on all flammable liquid containers when not unsung them-IFC 2701.3.3.5 9). Fire drill shall be conducted. Date and time o be determined by 2-21-06 |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR00053
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2006 | INSP - REINSPECTION | EGRIFFIN | Approved | all ok. fire drill set for 7-3-06 |