Case: T06FR00053

Parcel: 11720019A


Addresses:

181 W BROADWAY BL


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T06FR00053

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
01/17/2006 INSP - FULL Violation 1). Basement- Holes in ceiling by galley area, laundry room, and small storage room, shall have ceilings tiles maintained. IFC 703.
2). Fire alarm test indicates that horns were not sounded during test. This shall be submitted to plans review for approval. IFC 901.6
3). Mech. Room. All J-Boxes shall be covered. IFC 605.1
4). Replace glass on standpipe cabinets in floor of parking garage. IFC 901.6
5). All doors with door closures shall be closed at all times. IFC 703.2.2.
6). Old trash shoot shall be cleaned out entirely and sealed. IFC 703.1
7). All combustibles shall be 30 inches from electrical panels. IFC 605.23
8). All caps, and lids on all flammable liquid containers when not unsung them-IFC 2701.3.3.5
9). Fire drill shall be conducted. Date and time o be determined by 2-21-06