Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

12/14/2005

Applicant:

NOLA DEVELOPMENT LTD PARTNERSHIP

Description:

Full inspection

Outstanding Inspections

Case Number: T05FR01912
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/12/2006 INSP - REINSPECTION BCOBB Violation No problems addressed or abated at time of reinspection dated 1/5/06. Pre-citation issued. Reinspection set for 1/20/06.
01/12/2006 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Breaker Panel: Found 12/13/05 TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Move water cooler from in front of panel. TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 2. Remove tape from breaker switches.
01/12/2006 VIOL - FIRE RESIST.RATED CONST BCOBB Violation Sprinklers and ceiling: Found 12/13/05 TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained.
01/12/2006 VIOL - FIRE PROTECTION SYSTEMS BCOBB Violation TFC 901.6 Sprinklers: Found 12/13/05 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times. 1. The sprinkler system must be inspected, tested, and documented as to adequate coverage.
01/12/2006 VIOL - MEANS OF EGRESS BCOBB Violation Exit doors: Found 12/13/05 TFC 1008.1.8.3 Locks and latches. 1. There shall be a sign placed at the exit stating "These doors to remain unlocked when building is occupied" facing the egress side on front door. 2. Rear door to be clear and have a thumb latch. Exit signs: TFC 1011.1 Where required. 1. Rear door and door leading to the rear door (office) to each have a paper EXIT sign. TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. 1. Emergency lighting shall be installed in the proximity of the rear exit. 2. South emergency lights shall be operational. 3. Front Exit sign to be lit at all times.
12/14/2005 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code violations: