Case: T05FR01912
Case Details
Entered Date:
12/14/2005
Applicant:
NOLA DEVELOPMENT LTD PARTNERSHIP
Description:
Full inspection
Outstanding Inspections
Case Number: T05FR01912
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2006 | INSP - REINSPECTION | BCOBB | Violation | No problems addressed or abated at time of reinspection dated 1/5/06. Pre-citation issued. Reinspection set for 1/20/06. |
01/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Breaker Panel: Found 12/13/05 TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Move water cooler from in front of panel. TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 2. Remove tape from breaker switches. |
01/12/2006 | VIOL - FIRE RESIST.RATED CONST | BCOBB | Violation | Sprinklers and ceiling: Found 12/13/05 TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. |
01/12/2006 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Violation | TFC 901.6 Sprinklers: Found 12/13/05 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times. 1. The sprinkler system must be inspected, tested, and documented as to adequate coverage. |
01/12/2006 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Exit doors: Found 12/13/05 TFC 1008.1.8.3 Locks and latches. 1. There shall be a sign placed at the exit stating "These doors to remain unlocked when building is occupied" facing the egress side on front door. 2. Rear door to be clear and have a thumb latch. Exit signs: TFC 1011.1 Where required. 1. Rear door and door leading to the rear door (office) to each have a paper EXIT sign. TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. 1. Emergency lighting shall be installed in the proximity of the rear exit. 2. South emergency lights shall be operational. 3. Front Exit sign to be lit at all times. |
12/14/2005 | INSP - FULL | BCOBB | Violation | Please correct the following Tucson Fire Code violations: |