Case: T05FR01912

Parcel: 12108001B

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T05FR01912

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
01/12/2006 VIOL - MEANS OF EGRESS Violation Exit doors: Found 12/13/05
TFC 1008.1.8.3 Locks and latches.
1. There shall be a sign placed at the exit stating "These doors to remain unlocked when building is occupied" facing the egress side on front door.
2. Rear door to be clear and have a thumb latch.
Exit signs:
TFC 1011.1 Where required.
1. Rear door and door leading to the rear door (office) to each have a paper EXIT sign.
TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
1. Emergency lighting shall be installed in the proximity of the rear exit.
2. South emergency lights shall be operational.
3. Front Exit sign to be lit at all times.