Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Breaker Panel: Found 12/13/05 TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Move water cooler from in front of panel. TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 2. Remove tape from breaker switches. |