Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T05FR01912
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Breaker Panel: Found 12/13/05 TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Move water cooler from in front of panel. TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 2. Remove tape from breaker switches. |