Case: T05FR01303
Case Details
Entered Date:
08/22/2005
Applicant:
D RAGEL ENTERPRISES LLC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01303
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 21
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
08/15/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy. |
08/15/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained a minimum of 2 feet below the ceiling. |
08/15/2005 | VIOL - EMERGENCY PLAN/PREPARE | JLANGEJA | Violation | TFC 407.5- Where required by the fire code official, a Hazardous Materials Inventory Statement shall be submitted. |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space 30 x 36 x 78 shall be provided. (old mechanic shop) |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" W, 36" D, 78" H shall be provided in front of electrical service equipment. |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (accounting office) |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. Receptacle needs cover plate. |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes shall be prohibited. 1. holes in j-boxes and service panels 2. service panel needs blanks. (panel C) 3. sheet rock shall be replaced to protect wiring |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes shall be prohibited. (old mechanic shop) |
08/15/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistance-rated construction shall be maintained. 1. Ceiling tile in retail area 2. ceiling in closet |
08/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. |
08/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (old mechanic shop) |
08/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.6- Fire extinguishers shall not be obscured from view and some means provided to indicate its location. |
08/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.6- Fire extinguishers shall not be obstructed or obscured from view. (lobby) |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- Emergency lighting shall be provided in the event of a power failure. They shall automatically illuminate exit access corridors, passageways and aisles. |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.2- Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons. |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.1- Exits shall be marked by an approved exit sign readily visible from any direction of egress travel. (accounting office) |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.11.1- The MAQ of class III oxidizers shall be 1150 lbs. (solids) and 115 gallons (liquids). |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.Hazard identification signs shall be visible. |
08/15/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured from accidental dislodgement. |