Case: T05FR01303

Parcel: 13602001G


Addresses:

7960 E 22ND ST


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T05FR01303

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. Receptacle needs cover plate.
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" W, 36" D, 78" H shall be provided in front of electrical service equipment.
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes shall be prohibited.
1. holes in j-boxes and service panels
2. service panel needs blanks. (panel C)
3. sheet rock shall be replaced to protect wiring
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (accounting office)
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes shall be prohibited. (old mechanic shop)
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space 30 x 36 x 78 shall be provided. (old mechanic shop)