Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1008.1.2- Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons. |
| 08/15/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1011.1- Exits shall be marked by an approved exit sign readily visible from any direction of egress travel. (accounting office) |
| 08/15/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1006.3- Emergency lighting shall be provided in the event of a power failure. They shall automatically illuminate exit access corridors, passageways and aisles. |