Case: T05FR01040
Case Details
Entered Date:
07/07/2005
Applicant:
GEE ROSE TR
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01040
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 21
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
06/30/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage shall be maintained a minimum of 18" below sprinkler head deflectors. (attic space, several areas throughout) |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. Wires shall be terminated in a junction box or removed. (W ceiling) |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. (kitchen) |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. (kitchen)(office) |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (in market area) 1. by rear exit 2. near SW corner 3. on ceiling in center 4. NW corner |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (x 2 in office) |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes shall be prohibited. (walk in cooler) |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC Open junction boxes and open wiring splices shall be prohibited. (behind ice machine, S wall)(walk in cooler)(kitchen) |
06/30/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistive-rated construction shall be maintained. All holes in ceiling tiles shall be repaired. |
06/30/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- The required fire resistive-rated construction shall be maintained. The closet in the office shall be separated from the attic space. |
06/30/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (near restrooms) |
06/30/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6.2- Records of all fire protection system inspections, tests and maintenance required shall be kept on the premises for a minimum of 3 years. |
06/30/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 904.11.6.3- Hoods, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Records shall be kept on premises. |
06/30/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hanger or bracket. (kitchen) |
06/30/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hanger or bracket. (near restroom) |
06/30/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- The path of egress travel shall not be interrupted. Boxes shall not be allowed to accumulate in exit path. (outside) |
06/30/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- The path of egress travel shall not be interrupted. The South exit shall be kept clear at all times. |
06/30/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8- Doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (kitchen) |
06/30/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. (kitchen) |
06/30/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1013.2- Exit sign in SE corner of market shall be removed. (through kitchen) Egress from a room or space shall not pass through kitchens. |