Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T05FR01040
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC Open junction boxes and open wiring splices shall be prohibited. (behind ice machine, S wall)(walk in cooler)(kitchen) | |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. (kitchen) | |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. (kitchen)(office) | |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes shall be prohibited. (walk in cooler) | |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (x 2 in office) | |
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (in market area) 1. by rear exit 2. near SW corner 3. on ceiling in center 4. NW corner |
|
06/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Identified electrical hazards shall be abated. Wires shall be terminated in a junction box or removed. (W ceiling) |