Case: T05FR01040

Parcel: 131010250


Addresses:

4828 E 22ND ST


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T05FR01040

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC Open junction boxes and open wiring splices shall be prohibited. (behind ice machine, S wall)(walk in cooler)(kitchen)
06/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. (kitchen)
06/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. (kitchen)(office)
06/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes shall be prohibited. (walk in cooler)
06/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (x 2 in office)
06/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (in market area)
1. by rear exit
2. near SW corner
3. on ceiling in center
4. NW corner
06/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Identified electrical hazards shall be abated. Wires shall be terminated in a junction box or removed. (W ceiling)