Case: T05FR00920
Case Details
Entered Date:
06/20/2005
Applicant:
MALONE RALPH A TR 1/2 & MALONE GROUP 1/2
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00920
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 15
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
06/20/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- Certificate of Occupancy required. |
06/20/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained a minimum of 2 feet below ceiling in an unsprinklered building. |
06/20/2005 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | TFC 505.1- Address numbers shall be in accordance with Pima County Address display requirements. |
06/20/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. cord on charger for fork lift 2. damaged receptacle on N wall 3. damaged switch box on S wall 4. overhead wiring in warehouse #2 |
06/20/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other devise not complying with the ICC Electrical Code shall be prohibited. 1. time clock office 2. warehouse #1 incandescent lighting throughout |
06/20/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. 1. to neon sign over front door 2. in closet, runs into attic space 3. time clock office 4. invoice room 5. in warehouse #1 (several throughout) 6. to warehouse florescent lighting 7. in warehouse #2 |
06/20/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistive rated construction shall be maintained. Opening to attic space shall be covered. |
06/20/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (x 3) |
06/20/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be mounted on hangers or brackets and anchored securely. (office, warehouse #2) |
06/20/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8- Doors shall be readily openable from the eggress side without the use of a key, special knowledge or effort. Remove hasp and latch. |
06/20/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8.3- A readil visible durable sign shall be posted above the door stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". The letters shall be 1" on a contrasting background. |
06/20/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1009.11- Stairways shall have handrails. Rails shall not be less than 34" and not greater than 38" from the tread and shall be continuous to the nose of the last riser. |
06/20/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1012.1- Guards shall be located along open-sided walking surfaces which are located more than 30" above grade. Guards shall be of adequate strength. |
06/20/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1012.2- Guards shall form a protective barrier not less than 42" high. |