Case: T05FR00920

Parcel: 129043020


Addresses:

405 S CAMPBELL AV


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T05FR00920

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/20/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring.
1. to neon sign over front door
2. in closet, runs into attic space
3. time clock office
4. invoice room
5. in warehouse #1 (several throughout)
6. to warehouse florescent lighting
7. in warehouse #2
06/20/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other devise not complying with the ICC Electrical Code shall be prohibited.
1. time clock office
2. warehouse #1 incandescent lighting throughout
06/20/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Identified electrical hazards shall be abated.
1. cord on charger for fork lift
2. damaged receptacle on N wall
3. damaged switch box on S wall
4. overhead wiring in warehouse #2