Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T05FR00920
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. 1. to neon sign over front door 2. in closet, runs into attic space 3. time clock office 4. invoice room 5. in warehouse #1 (several throughout) 6. to warehouse florescent lighting 7. in warehouse #2 |
|
06/20/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other devise not complying with the ICC Electrical Code shall be prohibited. 1. time clock office 2. warehouse #1 incandescent lighting throughout |
|
06/20/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. cord on charger for fork lift 2. damaged receptacle on N wall 3. damaged switch box on S wall 4. overhead wiring in warehouse #2 |