Case: T05FR00920

Parcel: 129043020


Addresses:

405 S CAMPBELL AV


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T05FR00920

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
06/20/2005 VIOL - MEANS OF EGRESS Violation TFC 1008.1.8.3- A readil visible durable sign shall be posted above the door stating "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". The letters shall be 1" on a contrasting background.
06/20/2005 VIOL - MEANS OF EGRESS Violation TFC 1008.1.8- Doors shall be readily openable from the eggress side without the use of a key, special knowledge or effort. Remove hasp and latch.
06/20/2005 VIOL - MEANS OF EGRESS Violation TFC 1009.11- Stairways shall have handrails. Rails shall not be less than 34" and not greater than 38" from the tread and shall be continuous to the nose of the last riser.
06/20/2005 VIOL - MEANS OF EGRESS Violation TFC 1012.1- Guards shall be located along open-sided walking surfaces which are located more than 30" above grade. Guards shall be of adequate strength.
06/20/2005 VIOL - MEANS OF EGRESS Violation TFC 1012.2- Guards shall form a protective barrier not less than 42" high.