Status:

PRECITE

Type:

INSPECTION
Address:

Entered Date:

04/01/2005

Applicant:

HOTEL CORPORATION OF DOWNTOWN TUCSON

Description:

inspection

Outstanding Inspections

Case Number: T05FR00452
Case Status: PRECITE
Case Description: INSPECTION
Total Outstanding Inspections - 15
End Date Description Inspector Results Comments
04/01/2005 INSP - FULL EGRIFFIN Violation 1). The fire alarm inspection report dated 11-23-04, indicates, the following alarm components must be repaired, and they are; All heat detectors noted on report, 8th floor circuit. Invoice of work done shall be confirmation of repair. TFC 906.1
04/01/2005 INSP - FULL EGRIFFIN Violation 10). Doors equipped with door closures shall ALWAYS remain closed.. This includes ALL doors on all floors and ALL housekeeping chutes for cloth and trash.. TFC 703.2.2.
04/01/2005 INSP - FULL EGRIFFIN Violation 11). Extinguisher cabinets need keys for maintenance to be performed. TFC 906.1 Portable fire extinguisher classes are available at your request.
04/01/2005 INSP - FULL EGRIFFIN Violation 2). Fire pump shall be tested and report submitted to Tucson Fire Department. TFC 913.5
04/01/2005 INSP - FULL EGRIFFIN Violation 3). Currently laundry room sprinkler heads are dusty and covered with lint. These shall be cleaned. TFC 906.1
04/01/2005 INSP - FULL EGRIFFIN Violation 4). Basement: Ceiling tiles are missing in several places, galley area and kitchen. These shall be replaced. TFC 703.1
04/01/2005 INSP - FULL EGRIFFIN Violation 5). Poca Cosa: Exit light out of service, in entrance, shall be repaired. TFC 1026.3
04/01/2005 INSP - FULL EGRIFFIN Violation 6). Sprinkler in main entrance is corroded and shall be replaced. TFC 906.1
04/01/2005 INSP - FULL EGRIFFIN Violation 7). Outside Poca Cosa: Drywall around dumpster area is requires to be ! Hour construction. Shall be repaired. TFC 703.1
04/01/2005 INSP - FULL EGRIFFIN Violation 8). Remove extension cord to soda machines. TFC 605.5
04/01/2005 INSP - FULL EGRIFFIN Violation 9). Pool chemical storage has excessive leaves and rags; all shall be cleaned or removed. 304.1
05/06/2005 INSP - REINSPECTION EGRIFFIN Violation 1). The fire alarm inspection report dated 11-23-04, indicates, the following alarm components must be repaired, and they are; All heat detectors noted on report, 8th floor circuit. Invoice of work done shall be confirmation of repair. TFC 906.1
05/06/2005 INSP - REINSPECTION EGRIFFIN Violation 2). Fire pump shall be tested and report submitted to Tucson Fire Department. TFC 913.5
05/06/2005 INSP - REINSPECTION EGRIFFIN Violation 3). Currently laundry room sprinkler heads are dusty and covered with lint. These shall be cleaned. TFC 906.1
05/06/2005 INSP - REINSPECTION EGRIFFIN Violation 4). Sprinkler in main entrance is corroded and shall be replaced. TFC 906.1