Case: T05FR00452

Parcel: 11717023B


Addresses:

88 E BROADWAY BL


Inspection Status: Violation

Inspection History: INSP - REINSPECTION

Case Number - T05FR00452

Inspection Description - INSP - REINSPECTION

Inspection Status - Violation

Date Description Inspector Results Comments
05/06/2005 INSP - REINSPECTION Violation 1). The fire alarm inspection report dated 11-23-04, indicates, the following alarm components must be repaired, and they are;
All heat detectors noted on report, 8th floor circuit. Invoice of work done shall be confirmation of repair. TFC 906.1
05/06/2005 INSP - REINSPECTION Violation 2). Fire pump shall be tested and report submitted to Tucson Fire Department. TFC 913.5
05/06/2005 INSP - REINSPECTION Violation 3). Currently laundry room sprinkler heads are dusty and covered with lint. These shall be cleaned. TFC 906.1
05/06/2005 INSP - REINSPECTION Violation 4). Sprinkler in main entrance is corroded and shall be replaced. TFC 906.1