Inspection History Details
Inspection Status: Violation
Inspection History: INSP - REINSPECTION
Case Number - T05FR00452
Inspection Description - INSP - REINSPECTION
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2005 | INSP - REINSPECTION | Violation | 1). The fire alarm inspection report dated 11-23-04, indicates, the following alarm components must be repaired, and they are; All heat detectors noted on report, 8th floor circuit. Invoice of work done shall be confirmation of repair. TFC 906.1 |
|
05/06/2005 | INSP - REINSPECTION | Violation | 2). Fire pump shall be tested and report submitted to Tucson Fire Department. TFC 913.5 | |
05/06/2005 | INSP - REINSPECTION | Violation | 3). Currently laundry room sprinkler heads are dusty and covered with lint. These shall be cleaned. TFC 906.1 | |
05/06/2005 | INSP - REINSPECTION | Violation | 4). Sprinkler in main entrance is corroded and shall be replaced. TFC 906.1 |