Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T05FR00452
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2005 | INSP - FULL | Violation | 1). The fire alarm inspection report dated 11-23-04, indicates, the following alarm components must be repaired, and they are; All heat detectors noted on report, 8th floor circuit. Invoice of work done shall be confirmation of repair. TFC 906.1 |
|
04/01/2005 | INSP - FULL | Violation | 2). Fire pump shall be tested and report submitted to Tucson Fire Department. TFC 913.5 | |
04/01/2005 | INSP - FULL | Violation | 3). Currently laundry room sprinkler heads are dusty and covered with lint. These shall be cleaned. TFC 906.1 | |
04/01/2005 | INSP - FULL | Violation | 4). Basement: Ceiling tiles are missing in several places, galley area and kitchen. These shall be replaced. TFC 703.1 | |
04/01/2005 | INSP - FULL | Violation | 5). Poca Cosa: Exit light out of service, in entrance, shall be repaired. TFC 1026.3 | |
04/01/2005 | INSP - FULL | Violation | 6). Sprinkler in main entrance is corroded and shall be replaced. TFC 906.1 | |
04/01/2005 | INSP - FULL | Violation | 7). Outside Poca Cosa: Drywall around dumpster area is requires to be ! Hour construction. Shall be repaired. TFC 703.1 | |
04/01/2005 | INSP - FULL | Violation | 8). Remove extension cord to soda machines. TFC 605.5 | |
04/01/2005 | INSP - FULL | Violation | 9). Pool chemical storage has excessive leaves and rags; all shall be cleaned or removed. 304.1 | |
04/01/2005 | INSP - FULL | Violation | 10). Doors equipped with door closures shall ALWAYS remain closed.. This includes ALL doors on all floors and ALL housekeeping chutes for cloth and trash.. TFC 703.2.2. | |
04/01/2005 | INSP - FULL | Violation | 11). Extinguisher cabinets need keys for maintenance to be performed. TFC 906.1 Portable fire extinguisher classes are available at your request. |