Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

05/26/2004

Applicant:

DE CONCINI MARY TR

Description:

Inspection done

Outstanding Inspections

Case Number: T04FR00111
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS CSCHULTZ Violation TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. - Shall remove open sign by front door or install an outlet, electrical cord can not run thourgh the ceciling.
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS CSCHULTZ Violation TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. - Shall remove all storage from front of the electrical panels in the storage room.
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS CSCHULTZ Violation TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Shall remove extension cord to cash register on eastside of building.
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS CSCHULTZ Violation TFC 605.6 Unapproved Conditions. Approved covers shall be provided for all switch and electrical outlet boxes. - Shall replace missing cover plate to radio in kitchen area.
05/10/2004 VIOL - MEANS OF EGRESS CSCHULTZ Violation TFC 1010.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. Shall repair all exit signs in building.

Completed Inspections

Case Status: FIELD
Case Number: T04FR00111
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
05/10/2004 VIOL - FIRE PROTECTION SYSTEMS CSCHULTZ Approved TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Shall have all fire extingushers inspected, this shall be done on a yearly bases.
05/10/2004 VIOL - FIRE PROTECTION SYSTEMS CSCHULTZ Approved TFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Shall have a up to date inspection done on hood extingushing system and a copy of the report sent to Fire Prevention at 797 E. Ajo.
05/10/2004 VIOL - FIRE PROTECTION SYSTEMS CSCHULTZ Approved TFC 904.11.6.3 Hood Cleaning. Shall clean filters to hood system, need to set up maintenance program to keep filters clean.
05/10/2004 VIOL - FIRE PROTECTION SYSTEMS CSCHULTZ Approved TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Shall have the hood system cleaned from roof top to kitchen area. When finished no grease shall be on roof.
05/10/2004 INSP - FULL CSCHULTZ Approved Full inspection done