Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T04FR00111
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2004 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Shall remove extension cord to cash register on eastside of building. |
|
05/10/2004 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. - Shall remove all storage from front of the electrical panels in the storage room. | |
05/10/2004 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6 Unapproved Conditions. Approved covers shall be provided for all switch and electrical outlet boxes. - Shall replace missing cover plate to radio in kitchen area. |
|
05/10/2004 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. - Shall remove open sign by front door or install an outlet, electrical cord can not run thourgh the ceciling. |