Case: T04FR00111

Parcel: 125081000


Addresses:

2419 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T04FR00111

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Shall remove extension cord to cash register on eastside of building.
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. - Shall remove all storage from front of the electrical panels in the storage room.
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6 Unapproved Conditions. Approved covers shall
be provided for all switch and electrical outlet boxes. - Shall replace missing cover plate to radio in kitchen area.
05/10/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. - Shall remove open sign by front door or install an outlet, electrical cord can not run thourgh the ceciling.